Ring Main Circuit Breaker

Inquire now

Ring Main Circuit Breaker

Click to enlarge image


Overview

  • PNC-GGS Ring Main Circuit Breaker is pad mounted fully deadfront switchgear for up to 25.8kV, 630A underground system, combining puffer load break switches and vacuum fault interrupters. PNC-GGS series switchgear incorporates grounding switches for every ways to provide added safety and faster operation.

  • Every bushing in this switchgear is installed with one set of CT and voltage sensor each, so all the electrical values of connected distribution system can be measured. And, combined with RTU and Protection Relay integrated control, FTU-RC100, this switchgear can be remotely operated from control center system (SCADA).

  • PNC-GGS series Ring Main Circuit Breaker has been fully certified in accordance with IEC 60265-1, ANSI C37.60 (1981) and ANSI/IEEE C37.71 (1984) to meet and exceed customer specifications.

Electrical Characteristics

Description
PNC-GRC44-12/T630
PNC-GRC44-24/T630
Maximum System Voltage
12 kV
25.8 kV
Rated Continuous Current
630 A
630 A
Electrical Operating Time
of CB (Close/Open)
Electrical Operating Time
of LBS (Close/Open)
70/30 ms
700 ms
each
70/30 ms
700 ms
each
Minimum Clearing Time of CB
2.7 cycle
2.7 cycle
Number of Mechanical
Operations of CB
Number of Mechanical
Operations of LBS
Number of Mechanical
Operations of Ground

10,000 times
5,000 times
1,000 times

10,000 times
5,000 times
1,000 times
Short Time Withstand
Current ( rms)
20 kA (4 sec)
12.5 kA (1 sec)
Breaking
Capacity
of LBS
Mainly
Active Load
Current
630 A
630 A
Cable
Charging
Current
Breaking
25 A
25 A
Magnetizing
Current
Breaking
21 A
21 A
Line
Charging
Current
Breaking
1.5 A
1.5 A
Closed Loop
Breaking
Current
630 A
630 A
Breaking Capacity of CB
20 kA
12.5kA
Insulation Level
Lightning
Impulse
Withstand
Voltage
85 kV BIL
125 kV BIL
Power
Frequency
Withstand
Voltage
42 kV
60 kV
DC Voltage
Withstand
Voltage
53 kV
78 kV
Partial
Discharge
Extinction
Level
19 kV
19 kV
Weight without Outer Enclosure
670 Kg (2CB 2SW)

Related Keywords: Ring Main Circuit Breaker