Features
- Application
The variety of application outdoor, indoor and a narrow installation area
- Rapidity transfer action
At main line trouble, 3-phase transfer time is up to 0.2s
- Transfer interrupted function at load line fault
The case of load line fault, over current, short circuit and earthing, main power is failure, at this time ALTS shall not be transfer to preparation power line by detected and observed failure voltage and current of load line.
- Electrical and mechanical interrupt system
At the same time, multi-power-source operating interception.
For prevent both power source closing at the same time, posses the safety interlocking mechanism.
- Safety
It used incoming and out-going power cable and termination suitable for ANSI/ IEEE 386, shall not be exposed high voltage discharge parts. Therefore, man and animal cannot electric shock.
- Reliable insulation and interrupting capacity
Experienced and mastery breaking part design including pure puffer principle makes the arcing time just half a cycle. Due to this, decomposition of SF6 gas from the arc is negligible and the insulation capacity of SF6 gas doesn't decrease during all service life.
Ratings
Type
|
GCS-32A (Indoor) |
GOS-32A (Out door) |
|
Rated Voltage (kV) |
25.8 |
|
Rated Frequency (Hz) |
60 |
|
Rated Current (A) |
630 / 1250 |
|
Short circuit Making current (kAp) |
65 |
|
Power frequency withstand voltage (kV) |
70 |
1 min |
Rated lightning Impulse withstand voltage (BIL) (kV) |
150 |
1.2x50µs |
Rated Short circuit withstand current (kA) |
25 |
1sec |
Transfer Time (Sec) |
< 0.2 |
|
Circuit Configuration |
3 Way 2 Switch |
3W-2S |
Rated Operating Voltage (DC V) |
24 |
|
Operating Method |
Automatic, Manual |
Stored Spring Energy |
Rated Gas Pressure (kgf/㎠G) |
0.8 |
at 20°C |
Weight |
450 |
520 |
|
Degree of Protection IEC 60529 |
IP4X |
IP53 |
|
Applied Standard |
IEC 60265-1 |
|
|
|
|
| |
|
|
|