Home > Buy Now > Other Electrical Equipment > Automatic Circuit Recloser
 


P&C Technologies Co., Ltd.
 
icon Gas Insulated Switchgear
icon MV Switchgear
icon FTU for Distribution Automatioin
icon Substation Automation
icon Numerical Protection Relays
icon Digital Power Meter
icon SCADA System

line

icon Company Profile
icon Selling Leads
icon Bulletin Board
icon Guest Book
icon Index

line



visitors: 8344
 
Contact us
P&C Technologies Co., Ltd.
[Korea]
Address:
#304, AnyangMegavalley, 799, Kwanyang-dong, Dongahn-gu, Anyang-si, Gyeonggi-do 431-767 Korea
Phone:
82-2-22408190
Contact name:
Deuy Park , Overseas & Marketing Manager
Inquire now









P&C Technologies Co., Ltd.
 
MV Switchgear

Automatic Circuit Recloser

Inquire now

Automatic Circuit Recloser

Click to enlarge image


Additional Features

I. Bushing

  • Porcelain bushing is standard. It is vertically mounted to the tank case. The inside bushing hole walls are treated with semi-conductive painting to shorten the gap between the copper stud and the bushing wall. This enables the switch to have good RIV characteristics and also good partial discharge control.
  • Alternatively, epoxy bushing and silicon rubber boot is also available. Silicon rubber boot is put on the epoxy bushing to increase the voltage insulation and to protect inner bushing from external impact. We have both IEEE 386 and DIN cable connecting interface standard.

II. Bushing Terminal

  • NEMA type flat bare terminal made of copper alloy is standard for bushing terminal. In accordance with local environments, customers can select Mold Cone and lead wire.
  • Standard NEMA type flat bare terminal for Pollution Density 0.06 mg/cm2
  • Optionally Mold cone and lead wire of insulated copper conductor is helpful for high pollution (Pollution Density 0.35 mg/cm2) and salt fog area.
  • Insulation Cable filled with anti-water-penetration jelly together with bird-guard cap

III. Auxiliary Box

  • Supplement magnetic actuator mechanism, relay and Protection PCB are located inside the Auxiliary Box attached underneath the tank case. These components are connected to the control unit through control cable.

Electrical Characteristics

Description
PNC-RC-12/T630
PNC-RC-24/T630
Rated Maximum Voltage
12 kV
25.8 kV
Rated Continuous Current
630 A
630 A
Power Frequency Withstand Voltage
(dry-1min / wet -10sec)
42kV
60 kV
Lightening Impulse Withstand Voltage (BIL)
85 kV
150 kV
Rated Fault Making Capacity (peak)
50 kAp
32.5 kAp
Rated Short Circuit Interrupting Current
20 kA
12.5 kA
Mechanical/Electrical Operations
10,000 times
10,000 times
Weight without Mounting Frame
235 Kg
265 Kg

 